RV generator sizing, connections and safe operation

Choose an RV generator from its continuous output, compatible connection and ability to start the actual loads while supplying what is already running. Check fuel and altitude conditions as well as the air-conditioner manual. A model name, peak wattage or locked-rotor amps multiplied by voltage cannot settle the match alone.

A 2200 model does not provide 2200 watts continuously

Honda lists EU2200i output as 2,200 W maximum and 1,800 W rated. With an assumed 1,500-W running load and 400-W charger load, the total is 1,900 W, or 100 W above the rated output, before any startup requirement.

Assumed simultaneous running demandRunning appliance: 1,500 W; Charger: 400 WAssumed simultaneous running demandRunning appliance: 1,500 WCharger: 400 W

This example is not a tested air-conditioner pairing. Use the actual demand, outlet and cord ratings. Parallel operation requires manufacturer-approved compatible models and equipment; do not assume two model-name wattages simply become usable output at every receptacle.

Read Dometic’s guidance with its qualification

The September 2016 Dometic manual lists general generator guidance of 3.5 kW for one specified roof unit and 5 kW for two, with total RV usage, altitude and maintenance still relevant. Identify the exact model and controls before transferring that guidance.

Compressor locked-rotor current is not a complete startup waveform. Current times voltage gives apparent power without a power-factor qualification, not automatically real watts; it also does not describe the duration and voltage response of a start. Check the generator and appliance guidance or an approved verified pairing.

Altitude and fuel can change the usable output

The Onan KY operator manual gives 3,720 W at 2,500 feet and 3,300 W at 5,500 feet for its 4.0-kW example. That is 420 W less at the higher altitude. It is that manual’s example, not a derating table for every portable or another fuel configuration.

Resolve the whole supply arrangement
QuestionEvidence to obtain
Running and startup demandActual appliances and manufacturer matching guidance
Fuel and elevationExact generator’s rating and operating instructions
Connection and transferApproved inlet, transfer and grounding/protection arrangement
Site useCurrent generator permission, hours and noise rules
Storage and serviceModel-specific hour and calendar intervals

Portable exhaust and installed exhaust need their correct instructions

CPSC’s portable-generator guidance requires outdoor operation away from openings and warns against enclosed use. Never run a portable in an RV bay, garage or partly enclosed space. A permanent onboard unit instead requires its approved installation, maintained exhaust and own operating instructions.

A working CO alarm does not make exhaust exposure acceptable. Use portable generator care, Onan care and battery power stations versus portable generators for the actual equipment and operating decision.